Advertisment

AMI LT-600

author-image
PCQ Bureau
New Update

The LT 600 has a simple front panel with a switch and three

LEDs. The back panel has two outlets and an RS 232 port.

Advertisment

AMI

LT-600

A 600 VA offline UPS with two power

outlets. Good regulation, though the unit tested was not able to do a full cold-start on

battery. Optional software (not tested). Good value. Rs 11,950. Ranking: 4 (of 17

tested) Efficiency: 84% at 320 W Switchover time: 4.4 ms Backup time:

4 minutes

Like the other leaders, the LT’s battery float

voltage too was outside the limits and its maximum output voltage was 245 V, 11 percent

above 220V. Bar this, the LT gave good performance and was able to cold start an

additional 250 VA load, providing 231 V when already on. However, it was unable to do a

total cold start (switch on from batteries without mains support). According to the

vendor, their new models now available, can do a total cold start. However, these were

unavailable at the time of review, and could not be rated.

On short circuiting, the unit survived with an overload

indication and began functioning normally when mains was restored.

Advertisment